Heizka Security Control Cable
Heizka Control Cables are designed for reliable signal and control transmission in harsh environments, manufactured with premium materials to hold consistent technical characteristics. The range covers shielded 14 AWG, 16 AWG and 18 AWG constructions in one-pair and two-pair configurations, all rated 300 V with HDPE insulation, an aluminum foil screen and a gray PVC jacket. Choose these cables where your project requires dependable transmission, a robust protective jacket and proven materials for long-term operation.
Where This Range Is Used
Typical applications are Building Management Systems (BMS), industrial control panels, PLC and SCADA I/O, HVAC control and general factory automation, where signal integrity and stable uptime are critical. The datasheets also list indoor remote control of security systems, intercoms, audio distribution, door controllers, proximity sensors, keypads, access control and smoke detector wiring. The common thread is low-voltage control traffic that has to stay clean in an electrically noisy building.
Published Specifications
ProductConductorPublished electrical dataJacket
Heizka 14 AWG Shielded CableTinned copper8.2 Ω/km; 97 ± 3 pF/m conductor to conductor; 174 ± 3 pF/m conductor to shield; 1000 V insulation test0.6 mm average, 9.8 ± 0.3 mm OD
14 AWG Shielded Cable 2 PairStranded / solid bare copperNot publishedNot published
16 AWG Shielded CableStranded / solid bare copper, twistedNot publishedNot published
16 AWG Shielded Cable 2 PairStranded / solid bare copperNot publishedNot published
Heizka 18 AWG Shielded Cable 1 PairStranded / solid bare copperNot publishedNot published
Heizka 18 AWG Shielded Cable 2 PairStranded / solid bare copperNot publishedNot published
Every item carries HDPE insulation, an aluminum foil screen and a gray PVC jacket, is rated 300 V, and is supplied at 305 m per box with sequential length markings on the jacket, declared ISO 9001:2008 and RoHS. Where a specification calls for a capacitance, resistance or diameter figure on the 16 AWG or 18 AWG items, request the datasheet rather than interpolating from the 14 AWG values.
Selecting a Gauge and Pair Count
Gauge selection on control circuits is a volt-drop and load question, not a signal-quality question. An 18 AWG pair is normally sufficient for dry-contact inputs, sensor returns and low-current digital I/O over moderate distances. Move to 16 AWG where the run is longer or the loop holds a relay coil, and to 14 AWG for sustained loads or long runs between panels, where the published 8.2 Ω/km gives the most headroom. Two-pair versions cut installed cable count where a device needs both a power feed and a signal pair, but a single physical failure then affects two circuits, so keep independent or redundant functions on separate cables.
Screen Termination Practice
The aluminum foil screen only works if it is terminated. Bond it at the control panel or cabinet end only, keep the drain wire continuous through every junction box, and isolate the screen from enclosures and conduit at the field end so no ground loop is formed. The screen is never a circuit conductor or an equipment grounding conductor. Physical separation from power feeders, drives and busways remains the primary noise control measure, with the screen as a supplement. The same reasoning applied to life-safety circuits is set out in shielded versus unshielded fire-resistant cable.
These Cables Are Not Fire-Rated
This range uses HDPE insulation and a PVC jacket, and the listings do not cite any circuit-integrity or fire-performance standard such as IEC 60331, EN 50200 or BS 6387. Do not substitute a control cable into a fire alarm, voice evacuation, emergency lighting or smoke-control circuit. Those require the LSZH fire-resistant construction in the Heizka Fire Cable range, for example 2×1.5 mm². The distinction is explained in fire-resistant versus flame-retardant cable, and the cabling solutions overview shows how the ranges are applied together.
Frequently Asked Questions
Is the conductor stranded or solid?
The 16 AWG and 18 AWG listings state stranded bare copper and solid bare copper; the 14 AWG listing states tinned copper. Confirm the construction on the datasheet for the part number, since stranding affects flex life and termination.
Can these cables be used outdoors or direct buried?
The published applications describe indoor use. No outdoor, UV or direct-burial rating is stated, so do not assume one. Request confirmation before specifying an exterior route.
What operating temperature range applies?
An operating temperature range is not published on these listings. If your specification requires one, ask the sales team to supply the figure in writing and download the current sheet from Project Documents.
For pricing, gauge and pair-count selection, box quantities or datasheets for a submittal, send the part number, quantity and destination through contact us. Describing the load, run length and noise environment lets the team confirm the right gauge and screen configuration on the first reply.