The Voltrix C10KL-Li (Tower) and R10KL-Li (Rack 2U) are 10 kVA / 9 kW high-frequency online double-conversion (VFI) UPS systems built on a 64-cell LiFePO4 external battery module (204.8 V). LiFePO4 chemistry delivers up to 3× the backup time of a comparable lead-acid UPS in a lighter, more compact footprint, with a service life exceeding 2,000 charge/discharge cycles. Runtime is set by the external battery module, which is ordered separately and sized to the autonomy required.
DSP digital control, active input power factor correction (> 0.99) and a wide 90 ~ 300 VAC input window make the pair fully compatible with generator sets and unstable grids. Dry contact and MODBUS (RS485) interfaces give direct BMS integration, and the 4-state lithium charger (CC / CV / Floating / Turn-off) can be customised to the battery pack. Both form factors share identical electrical performance — choose Tower for desktop or floor placement, or the 2U Rack model for standard 19-inch cabinets.
Technical Specifications — C10KL-Li / R10KL-Li — 10 kVA / 9 kW
| AC INPUT | |
|---|---|
| Input System | Single Phase (L/N+PE) |
| Nominal Voltage | 208/220/230/240 VAC |
| Voltage Range | 90 ~ 300 VAC |
| Frequency | 50 / 60 Hz |
| Frequency Range | (40 ~ 70) ± 0.5 Hz |
| Input Power Factor | > 0.99 |
| AC OUTPUT | |
| Output Wiring System | Single Phase (L/N+PE) |
| Inverter Output Voltage | 208/220/230/240 VAC ±1% |
| Output Frequency | 50/60 Hz ±4 Hz (Sync mode) 50/60 Hz ±0.1 (Fix freq. mode) |
| Waveform | Pure Sine Wave |
| Harmonic Distortion | THD < 2% (linear) THD < 8% (non-linear) |
| Overload Capability | 100~105%: continuous 105~125%: 10 min |
| 126~150%: 60 sec >150%: 0.3 sec | |
| Transfer Time | Line ↔ Battery: 0 ms |
| EFFICIENCY | |
| Line Mode | > 93% |
| Battery Mode | > 90% |
| LITHIUM BATTERY INPUT | |
| Charging Voltage | 204.8 V (64-cell LiFePO4, 3.2V/cell) Customisable on request |
| Battery Capacity | External Battery Module |
| Charging Current | 4A / 8A (optional, long backup model) |
| Charger Behaviour | CC · CV · Floating · Turn-off (4-state) |
| Protection | 3 over-voltage loop, over-temp / over-pressure interface |
| PHYSICAL | |
| Tower Dim. W×D×H (mm) | 190×562×340 |
| Rack Dim. W×H×D (mm) | 440×493×88 (2U) |
| Tower Net Weight (kg) | 13.5 |
| Rack Net Weight (kg) | 11.9 |
Key Features
- Online double-conversion (VFI) topology — 0 ms transfer, pure sine wave output
- LiFePO4 lithium battery, 64-cell (204.8 V) — more than 2,000 charge/discharge cycles
- Up to 3× backup time vs. a comparable lead-acid UPS, at a fraction of the weight
- Wide input range 90 ~ 300 VAC, (40 ~ 70) ± 0.5 Hz — generator compatible, cold start and ECO mode
- Active input power factor correction > 0.99
- Efficiency: line mode > 93%, battery mode > 90%
- 4-state lithium charger (CC / CV / Floating / Turn-off), charging current 4A / 8A (optional, long backup model)
- 50/60 Hz auto-sensing and frequency-converter mode
- RS232 standard; optional USB (1–3 kVA), SNMP / TCP-IP network card for remote monitoring, dry contact for BMS dominant control and MODBUS (RS485) card for BMS integration
10 kVA Long-Backup with a Lithium Battery Bank
The C10KL-Li / R10KL-Li delivers 10 kVA / 9 kW single-phase in and single-phase out, and runs from an external LiFePO4 battery module. It is aimed at a small server room, a multi-rack network core, or the central systems of a hospital, hotel or factory where the required autonomy is too long for an internal battery and where a lithium bank is preferred to a large lead-acid cabinet.
Battery Bank
The battery bank is listed as 64 LiFePO4 cells at 3.2 V per cell, which is 204.8 V nominal (64 × 3.2 V, calculated). Battery capacity is listed as “External Battery Module”, so runtime depends on the module selected. The charger uses four stages (constant current, constant voltage, floating, turn-off), with charging current listed as 4 A or 8 A (optional, long-backup model).
- Recharge check: recharge time can never be shorter than module capacity ÷ charging current. Agree the charging current with Heizka when the battery module is chosen.
- Runtime: request a runtime table for your actual load in kW, not in kVA, because the UPS output rating is 9 kW.
Electrical Planning
- Full-load input current is roughly 42.5 A at 230 V (9 kW ÷ 93% ÷ 0.99 ÷ 230 V, calculated, excluding charging current). This needs a dedicated, hard-wired supply circuit sized to local code.
- Output is single-phase 208/220/230/240 VAC ±1%. At 9 kW and 230 V the output current is about 39 A (calculated), so plan a protected output distribution board for the racks.
- Input voltage range is 90~300 VAC; input power factor is above 0.99; battery-mode efficiency is listed above 90%.
Compact Power Stage
Because the batteries sit in a separate module, the power unit itself is light: the tower is 190 × 562 × 340 mm at 13.5 kg, and the rack version is 2U, 440 × 493 × 88 mm at 11.9 kg. Plan the rack space for the battery modules separately.
Lithium or VRLA at 10 kVA?
For the same rating with a lead-acid bank, see the S10KL / RS10KL. Compare total battery weight, floor space and the planned battery replacement cycle for your site before choosing.
Related Models
- C6KL-Li / R6KL-Li — 6 kVA lithium long-backup.
- S20KL — 20 kVA with three-phase or single-phase input.
- L-Series lithium range.
Frequently Asked Questions
Can I order the C10KL-Li without the battery module?
The UPS is listed for use with an external battery module. Confirm the supply scope in your quote request.
Read how UPS power fits into data center infrastructure.
Ordering Information
| Voltrix Model | Form Factor | Apparent / Active Power | Battery | Part Number |
|---|---|---|---|---|
| C10KL-Li | Tower | 10 kVA / 9 kW | 64-cell LiFePO4 (204.8V) | VTX-C10KL-Li |
| R10KL-Li | Rack 2U | 10 kVA / 9 kW | 64-cell LiFePO4 (204.8V) | VTX-R10KL-Li |
Downloads
Certifications & Warranty
Designed and manufactured under ISO 9001:2015. CE (EU Declaration of Conformity), IEC/EN 62040-1 (UPS Safety), IEC/EN 62040-2 (UPS EMC — Class C2), RoHS 2011/65/EU. 2-year UPS system warranty, return-to-base, parts and labour; LiFePO4 battery warranty 2 years or 2,000 full charge-discharge cycles, whichever occurs first. 24/7 technical support with response within 4 hours.
Specifications subject to change without notice. Battery cycle life and backup time are indicative and may vary with operating temperature, load profile and discharge history. Voltrix is a registered brand of Heizka. All trademarks are property of their respective owners.