The Voltrix S3KL (Tower) and RS3KL (Rack 2U) are 3 kVA / 2.7 kW high-frequency online double-conversion (VFI) UPS systems with a long-backup external battery bank (72V/96V). With 0 ms transfer time, input power factor correction of 0.99 at full load and a wide 60~300V (half load) 176~300V (full load) input window, they protect servers, network equipment and control systems against outages, sags, surges and frequency variation.
Both form factors share identical electrical performance; choose Tower for desktop or floor placement, or the 2U Rack model for standard 19-inch cabinets. The external battery module is ordered separately and sized to the autonomy required — runtime is therefore set by the battery bank, not by the UPS. A standard built-in-battery model (S3K / RS3K) is available separately.
Technical Specifications — S3KL / RS3KL — 3 kVA / 2.7 kW
| INPUT | |
|---|---|
| Topology | VFI Online Dbl. Conv. |
| Input Config | 1Φ L/N+PE |
| Nominal Input V | 110~127V or 220~240V |
| Input Range | 60~300V (half load) 176~300V (full load) |
| Input Freq. | 40 ~ 70 Hz |
| Input PF | 0.99 @ Full |
| OUTPUT | |
| Output Voltage | 230 VAC (220/240/208V) or 120 VAC |
| Volt. Regulation | ±1% |
| Freq (Sync Mode) | 46~54 Hz 57~63 Hz |
| Freq (Bat. Mode) | 50Hz±0.05 60Hz±0.05 |
| THDv Lin./Non-lin. | 2% / 6% |
| Waveform | Pure Sine |
| Transfer Line↔Bat | 0 ms |
| Transfer Inv↔Bypass | < 4 ms |
| EFFICIENCY | |
| AC → AC | 91% |
| ECO Mode | 96% |
| Battery Mode | 89% |
| BATTERY & CHARGER | |
| Battery Type | VRLA Lead Acid |
| Battery Config. | Ext. 72V/96V |
| Float Charge V | 81.8/109.2 V |
| Backup @50% Load | Per EBM |
| Recharge Time | Per EBM |
| Max Rech. Current | 6 A |
| Display / Comm. | LED/LCD RS232/USB |
| PHYSICAL | |
| Form Factor | Tower / Rack 2U |
| Tower W×H×L (mm) | 190×318×380 |
| Rack W×H×D (mm) | 438×88×350 |
| Net Weight (kg) | 10.8 |
| ENVIRONMENT | |
| Operating Temp. | 0~+40°C |
| Humidity | 5~97% RH Non-cond. |
Key Features
- Online double-conversion (VFI) topology — 0 ms transfer, pure sine wave output
- Input power factor 0.99 at full load — reduces wiring and energy costs
- Wide input range 60~300V (half load) 176~300V (full load), 40 ~ 70 Hz — generator compatible
- Long-backup external battery — max charging current 6 A; runtime set by the external battery module
- AC→AC efficiency 91%, ECO mode 96%
- LED/LCD display with RS232 + USB communication
Long Runtime at 3 kVA
The S3KL / RS3KL keeps the 3 kVA / 2.7 kW rating of the S3K and moves the battery outside the UPS. Runtime then depends on the external battery bank, so the same UPS can cover anything from a short generator start-up gap to several hours of autonomy. It is a common choice for a server cabinet at a branch office, a security control room, or the network core of a building where mains failures can be long.
External Battery Voltage
The listed external battery voltages are 72 V and 96 V, which is a string of 6 or 8 × 12 V blocks (72 ÷ 12 and 96 ÷ 12, calculated). Backup and recharge time are listed as “Per EBM”, meaning they follow the battery module chosen. The charger supplies up to 6 A.
Worked Runtime Example
This example only shows the method; it is not a Voltrix rating.
- Battery: 8 × 12 V / 100 Ah = 9,600 Wh nominal energy (calculated).
- Load: 1,350 W (50% of 2.7 kW).
- Simple ratio: 9,600 Wh ÷ 1,350 W ≈ 7.1 hours before losses (calculated). Real runtime will be lower once inverter losses, temperature and battery ageing are included, so use the battery maker’s constant-power discharge table for the final figure.
- Recharge: 100 Ah ÷ 6 A ≈ 17 hours as a minimum (calculated). If the site can expect repeated outages close together, size the battery bank with this recharge time in mind.
Size and Weight Compared with the S3K
| Item | S3KL / RS3KL | S3K / RS3K |
|---|---|---|
| Battery | External 72V/96V | Internal 6×12V/7AH |
| Tower W×H×L (mm) | 190×318×380 | 145×220×328 |
| Rack W×H×D (mm) | 438×88×350 | 438×88×350 |
| Net weight | 10.8 kg | 21.6 kg |
| Max charge current | 6 A | 1.5 A |
Note that the S3KL tower is larger than the S3K tower even though it carries no battery; allow for the 190 × 318 mm footprint when planning floor space.
Frequently Asked Questions
Should I choose lead-acid or lithium for long backup?
Both are available. The lithium C3K-Li / R3K-Li lists a LiFePO4 battery; compare weight, space and battery replacement plans for your site.
Can one battery bank be shared by two UPS units?
Not as standard. Plan one battery string per UPS unless Heizka confirms otherwise for your project.
See the VRLA UPS range and the data center infrastructure guide.
Ordering Information
| Voltrix Model | Form Factor | Apparent / Active Power | Battery | Part Number |
|---|---|---|---|---|
| S3KL | Tower | 3 kVA / 2.7 kW | Ext. 72V/96V Battery | VTX-S3KL |
| RS3KL | Rack 2U | 3 kVA / 2.7 kW | Ext. 72V/96V Battery | VTX-RS3KL |
Downloads
Certifications & Warranty
Designed and manufactured under ISO 9001:2015. CE (EU Declaration of Conformity), IEC/EN 62040-1 (UPS Safety), IEC/EN 62040-2 (UPS EMC — Class C2), RoHS 2011/65/EU. 2-year UPS system warranty, return-to-base, parts and labour; 1-year VRLA battery warranty. 24/7 technical support with response within 4 hours.
Specifications subject to change without notice. Backup times are indicative and depend on load, temperature, battery age and discharge history. Voltrix is a registered brand of Heizka. All trademarks are property of their respective owners.