The Voltrix S1KL (Tower) and RS1KL (Rack 2U) are 1 kVA / 0.9 kW high-frequency online double-conversion (VFI) UPS systems with a long-backup external battery bank (24V/36V). With 0 ms transfer time, input power factor correction of 0.99 at full load and a wide 60~300V (half load) 176~300V (full load) input window, they protect servers, network equipment and control systems against outages, sags, surges and frequency variation.
Both form factors share identical electrical performance; choose Tower for desktop or floor placement, or the 2U Rack model for standard 19-inch cabinets. The external battery module is ordered separately and sized to the autonomy required — runtime is therefore set by the battery bank, not by the UPS. A standard built-in-battery model (S1K / RS1K) is available separately.
Technical Specifications — S1KL / RS1KL — 1 kVA / 0.9 kW
| INPUT | |
|---|---|
| Topology | VFI Online Dbl. Conv. |
| Input Config | 1Φ L/N+PE |
| Nominal Input V | 110~127V or 220~240V |
| Input Range | 60~300V (half load) 176~300V (full load) |
| Input Freq. | 40 ~ 70 Hz |
| Input PF | 0.99 @ Full |
| OUTPUT | |
| Output Voltage | 230 VAC (220/240/208V) or 120 VAC |
| Volt. Regulation | ±1% |
| Freq (Sync Mode) | 46~54 Hz 57~63 Hz |
| Freq (Bat. Mode) | 50Hz±0.05 60Hz±0.05 |
| THDv Lin./Non-lin. | 2% / 6% |
| Waveform | Pure Sine |
| Transfer Line↔Bat | 0 ms |
| Transfer Inv↔Bypass | < 4 ms |
| EFFICIENCY | |
| AC → AC | 89% |
| ECO Mode | 94% |
| Battery Mode | 87% |
| BATTERY & CHARGER | |
| Battery Type | VRLA Lead Acid |
| Battery Config. | Ext. 24V/36V |
| Float Charge V | 27.3/41.0 V |
| Backup @50% Load | Per EBM |
| Recharge Time | Per EBM |
| Max Rech. Current | 6 A |
| Display / Comm. | LED/LCD RS232/USB |
| PHYSICAL | |
| Form Factor | Tower / Rack 2U |
| Tower W×H×L (mm) | 145×220×400 |
| Rack W×H×D (mm) | 438×88×350 |
| Net Weight (kg) | 6.1 |
| ENVIRONMENT | |
| Operating Temp. | 0~+40°C |
| Humidity | 5~97% RH Non-cond. |
Key Features
- Online double-conversion (VFI) topology — 0 ms transfer, pure sine wave output
- Input power factor 0.99 at full load — reduces wiring and energy costs
- Wide input range 60~300V (half load) 176~300V (full load), 40 ~ 70 Hz — generator compatible
- Long-backup external battery — max charging current 6 A; runtime set by the external battery module
- AC→AC efficiency 89%, ECO mode 94%
- LED/LCD display with RS232 + USB communication
Why Choose the Long-Backup S1KL / RS1KL
The S1KL and RS1KL keep the 1 kVA / 0.9 kW electrical design of the S1K but have no internal battery. Instead they connect to an external battery string, so runtime is set by the battery you choose, not by the UPS. This suits small loads that must stay up for a long time: a remote CCTV or telecom cabinet, an access control controller at a site entrance, a fire alarm network interface or a BMS controller in a plant room where the mains can be off for an extended period.
Planning the External Battery String
The model accepts a 24 V or 36 V external battery, which means a string of 2 or 3 × 12 V blocks (24 ÷ 12 and 36 ÷ 12, calculated). Backup time and recharge time are listed as “Per EBM” because they depend on the external battery module.
- First runtime estimate: stored energy (blocks × 12 V × Ah) divided by the load in watts. For example, 2 × 12 V × 40 Ah = 960 Wh. Real runtime is lower because of conversion losses, temperature and battery age, so confirm with the battery maker’s discharge table.
- Recharge check: the charger delivers up to 6 A, four times the 1.5 A of the standard S1K. Recharge time can never be shorter than capacity ÷ charge current; a 40 Ah string at 6 A needs at least about 7 hours (calculated).
- Cabling: keep the DC cable between UPS and battery short, sized for the discharge current, and protected as required by local code.
Physical Differences from the S1K
Because there is no battery inside, the S1KL weighs 6.1 kg against 8.9 kg for the S1K (2.8 kg lighter). The tower is deeper, 145 × 220 × 400 mm against 328 mm for the S1K. The RS1KL rack version stays at 2U (438 × 88 × 350 mm). Leave room next to the UPS for the battery cabinet or shelf, and check the floor or shelf rating for the battery weight.
Related Models
- S1K / RS1K — same rating with a built-in 2×12V/7AH battery for short bridge time.
- S2KL / RS2KL — 2 kVA / 1.8 kW long-backup model for larger loads.
- C1K-Li / R1K-Li — 1 kVA lithium (LiFePO4) option.
Frequently Asked Questions
Can the S1KL run without a battery connected?
It is designed to work with its external battery. Without one, there is no backup when the mains fails.
24 V or 36 V — which should I use?
Both are listed for this model. Confirm the setting and the battery module with Heizka when you request a quote.
Is the rack version the same electrically?
Yes. The S1KL and RS1KL differ only in enclosure.
Browse the VRLA UPS range or read about power in security and access control systems.
Ordering Information
| Voltrix Model | Form Factor | Apparent / Active Power | Battery | Part Number |
|---|---|---|---|---|
| S1KL | Tower | 1 kVA / 0.9 kW | Ext. 24V/36V Battery | VTX-S1KL |
| RS1KL | Rack 2U | 1 kVA / 0.9 kW | Ext. 24V/36V Battery | VTX-RS1KL |
Downloads
Certifications & Warranty
Designed and manufactured under ISO 9001:2015. CE (EU Declaration of Conformity), IEC/EN 62040-1 (UPS Safety), IEC/EN 62040-2 (UPS EMC — Class C2), RoHS 2011/65/EU. 2-year UPS system warranty, return-to-base, parts and labour; 1-year VRLA battery warranty. 24/7 technical support with response within 4 hours.
Specifications subject to change without notice. Backup times are indicative and depend on load, temperature, battery age and discharge history. Voltrix is a registered brand of Heizka. All trademarks are property of their respective owners.