The Voltrix S2K (Tower) and RS2K (Rack 2U) are 2 kVA / 1.8 kW high-frequency online double-conversion (VFI) UPS systems with a built-in maintenance-free VRLA battery (4×12V/7AH). With 0 ms transfer time, input power factor correction of 0.99 at full load and a wide 60~300V (half load) 176~300V (full load) input window, they protect servers, network equipment and control systems against outages, sags, surges and frequency variation.
Both form factors share identical electrical performance; choose Tower for desktop or floor placement, or the 2U Rack model for standard 19-inch cabinets. A long-backup external-battery variant (S2KL / RS2KL) is available separately.
Technical Specifications — S2K / RS2K — 2 kVA / 1.8 kW
| INPUT | |
|---|---|
| Topology | VFI Online Dbl. Conv. |
| Input Config | 1Φ L/N+PE |
| Nominal Input V | 110~127V or 220~240V |
| Input Range | 60~300V (half load) 176~300V (full load) |
| Input Freq. | 40 ~ 70 Hz |
| Input PF | 0.99 @ Full |
| OUTPUT | |
| Output Voltage | 230 VAC (220/240/208V) or 120 VAC |
| Volt. Regulation | ±1% |
| Freq (Sync Mode) | 46~54 Hz 57~63 Hz |
| Freq (Bat. Mode) | 50Hz±0.05 60Hz±0.05 |
| THDv Lin./Non-lin. | 2% / 6% |
| Waveform | Pure Sine |
| Transfer Line↔Bat | 0 ms |
| Transfer Inv↔Bypass | < 4 ms |
| EFFICIENCY | |
| AC → AC | 90% |
| ECO Mode | 95% |
| Battery Mode | 88% |
| BATTERY & CHARGER | |
| Battery Type | VRLA Lead Acid |
| Battery Config. | 4×12V/7AH (internal) |
| Float Charge V | 54.6 V |
| Backup @50% Load | ≥ 5 min |
| Recharge Time | ~5 h |
| Max Rech. Current | 1.5 A |
| Display / Comm. | LED/LCD RS232/USB |
| PHYSICAL | |
| Form Factor | Tower / Rack 2U |
| Tower W×H×L (mm) | 145×220×328 |
| Rack W×H×D (mm) | 438×88×350 |
| Net Weight (kg) | 17.5 |
| ENVIRONMENT | |
| Operating Temp. | 0~+40°C |
| Humidity | 5~97% RH Non-cond. |
Key Features
- Online double-conversion (VFI) topology — 0 ms transfer, pure sine wave output
- Input power factor 0.99 at full load — reduces wiring and energy costs
- Wide input range 60~300V (half load) 176~300V (full load), 40 ~ 70 Hz — generator compatible
- Maintenance-free VRLA battery, recharge ~5 h
- AC→AC efficiency 90%, ECO mode 95%
- LED/LCD display with RS232 + USB communication
Typical Loads for a 2 kVA Online UPS
At 1.8 kW the S2K / RS2K covers the step between a single network point and a full server rack. Common uses are a CCTV recorder with its PoE switch, a small file or application server with a firewall and core switch, a nurse-call or PA head-end, or the controller and network gear of a building management system. All of these are sensitive to a reboot, which is why the zero transfer time of online double conversion matters here.
How Much Backup to Expect
The published figure is ≥ 5 min at 50% load, which is about 900 W for this model. The internal battery is 4 × 12 V / 7 Ah, about 336 Wh of nominal stored energy (calculated). In practice this gives time to ride out short outages, to let a generator start and take the load, or to shut servers down cleanly through the RS232/USB link.
If the site needs more than a few minutes at this power, use the long-backup S2KL / RS2KL with an external battery string, or the lithium C2K-Li / R2K-Li, which lists 922 Wh of internal capacity.
Electrical Planning
- Full-load input current is roughly 8.8 A at 230 V (1.8 kW ÷ 90% ÷ 0.99 ÷ 230 V, calculated, excluding battery charging current).
- The 0.99 input power factor means the UPS draws close to its real power from the supply, which keeps upstream cable and generator sizing simple.
- Output can be set to 230 VAC (220/240/208 V) or 120 VAC, as listed in the specification table.
Installation Notes
- At 17.5 kg the RS2K should sit on rack rails or a fixed shelf, not hang from the front rack ears alone.
- The rack unit is 2U, 438 × 88 × 350 mm. Place heavy UPS units low in the rack to keep the centre of gravity down.
- The tower (145 × 220 × 328 mm) suits a comms room floor or a desk-side position.
- Keep the room within 0 to +40 °C; heat shortens VRLA battery life.
Compare Nearby Models
| Model | Active power | Internal battery | AC → AC efficiency |
|---|---|---|---|
| S1K / RS1K | 0.9 kW | 2×12V/7AH | 89% |
| S2K / RS2K | 1.8 kW | 4×12V/7AH | 90% |
| S3K / RS3K | 2.7 kW | 6×12V/7AH | 91% |
Frequently Asked Questions
Can I connect extra batteries to the S2K?
No. The S2K runs from its internal battery. For longer runtime choose the S2KL / RS2KL.
Is ECO mode suitable for servers?
ECO mode raises the listed efficiency from 90% to 95%. In online UPS designs generally, ECO mode trades some power conditioning for that efficiency, so many IT sites keep online mode for sensitive loads. Ask Heizka how ECO mode behaves on this model before enabling it.
See all VRLA UPS models or the data center infrastructure overview.
Ordering Information
| Voltrix Model | Form Factor | Apparent / Active Power | Battery | Part Number |
|---|---|---|---|---|
| S2K | Tower | 2 kVA / 1.8 kW | Internal VRLA (4×12V/7AH) | VTX-S2K |
| RS2K | Rack 2U | 2 kVA / 1.8 kW | Internal VRLA (4×12V/7AH) | VTX-RS2K |
Downloads
Certifications & Warranty
Designed and manufactured under ISO 9001:2015. CE (EU Declaration of Conformity), IEC/EN 62040-1 (UPS Safety), IEC/EN 62040-2 (UPS EMC — Class C2), RoHS 2011/65/EU. 2-year UPS system warranty, return-to-base, parts and labour; 1-year VRLA battery warranty. 24/7 technical support with response within 4 hours.
Specifications subject to change without notice. Backup times are indicative and depend on load, temperature, battery age and discharge history. Voltrix is a registered brand of Heizka. All trademarks are property of their respective owners.