The Voltrix S20KL is a 20 kVA / 18 kW high-frequency online double-conversion (VFI) tower UPS with an external VRLA battery cabinet sized to the required autonomy. It accepts a three-phase (or single-phase) input and delivers a single-phase output, with an ultra-wide 156 ~ 520 VAC input window, 0 ms transfer time and input power factor above 0.99 — making it suitable for generator sets and unstable grid environments.
The S20KL is the long-backup variant: the battery cabinet is ordered separately and sized to the autonomy required, so runtime is set by the cabinet rather than by the UPS. A standard built-in-battery model (S20K) is available separately.
Technical Specifications — S20KL — 20 kVA / 18 kW
| INPUT | |
|---|---|
| Topology | Online Double Conversion (VFI) |
| Input Config | 3Φ (L1/L2/L3/N)+PE or 1Φ L/N+PE |
| Nominal Input V | 380 / 400 / 415 VAC (3Φ) |
| Input Voltage Range | 156 ~ 520 VAC |
| Bypass Voltage Range | 310 ~ 450 VAC |
| Input Freq. Range | (40~70) Hz ±0.5 Hz |
| OUTPUT | |
| Output Voltage | 220 / 230 / 240 VAC ±2% |
| Output Freq (Sync) | 50/60 Hz ±4 Hz |
| Output Freq (Fix) | 50/60 Hz ±1% |
| THDv (Lin. / Non-lin.) | < 2% / < 7% |
| Transfer Time | 0 ms |
| Input Power Factor | > 0.99 |
| Output Waveform | Pure Sine Wave |
| EFFICIENCY | |
| Line / ECO / Battery | 94% / >95% / 93% |
| BATTERY & CHARGER | |
| Battery Type | VRLA Sealed Lead Acid |
| Battery Config. | 192V External Cabinet |
| Battery Voltage | 192 VDC (240V charge) |
| Backup @50% / 100% | Per EBM |
| Recharge Time / Curr. | Per EBM / 4 A |
| Communication | RS232 + USB / SNMP (opt.) |
| PHYSICAL | |
| Form Factor | Tower |
| Dimensions W×D×H (mm) | 581×239×529 |
| Net / Gross Weight | 26 kg / 33.5 kg |
| Acoustic Noise | < 55 dB(A) |
| ENVIRONMENT | |
| Operating Temp. | 0 ~ +40°C |
| Humidity | 5 ~ 97% RH (Non-condensing) |
Key Features
- Online double-conversion (VFI) topology — 0 ms transfer, pure sine wave output
- Three-phase or single-phase input, single-phase output — 3Φ (L1/L2/L3/N)+PE or 1Φ L/N+PE
- Ultra-wide input range 156 ~ 520 VAC, (40~70) Hz ±0.5 Hz — generator compatible
- Input power factor > 0.99
- Efficiency (line / ECO / battery): 94% / >95% / 93%
- Conformal coating — anti-corrosion for harsh environments
- RS232 + USB with SNMP (optional)
20 kVA with Extended Autonomy
The S20KL shares the 20 kVA / 18 kW power stage of the S20K — three-phase or single-phase input, single-phase output — but has no internal battery. It connects to an external 192 V battery cabinet, so autonomy can be planned for the site rather than fixed by the UPS. Typical projects include a server room that must keep running until a generator is refuelled, a control room for a security or traffic system, and telecom rooms on remote sites.
Battery Cabinet Planning
A 192 V string uses 16 × 12 V blocks (192 ÷ 12, calculated). Runtime and recharge time are listed as “Per EBM”, and the charger supplies up to 4 A.
| Example string (not a Voltrix pack) | Nominal energy | Simple ratio at 9 kW (50% load) | Minimum recharge at 4 A |
|---|---|---|---|
| 16 × 12 V / 65 Ah | 12,480 Wh | about 83 min | about 16 h |
| 16 × 12 V / 100 Ah | 19,200 Wh | about 128 min | about 25 h |
All values are calculated (blocks × 12 V × Ah; energy ÷ load; Ah ÷ charge current) and ignore conversion losses, temperature and battery ageing. Real runtime is lower; use the battery maker’s constant-power discharge data for the final design. The long recharge times show why the charger rating should be part of the battery decision, especially where outages can repeat.
Weight and Space
- The S20KL weighs 26 kg net (33.5 kg gross), against 88.7 kg for the S20K with internal batteries — about 62.7 kg lighter (calculated). The weight moves to the battery cabinet instead, so check the floor rating where the batteries will stand.
- Listed dimensions are 581 × 239 × 529 mm (W × D × H).
- Acoustic noise is listed below 55 dB(A).
Electrical Planning
At full load the input current is about 27.9 A per phase on a 400 V three-phase supply, or about 84 A on a 230 V single-phase supply, and the single-phase output current is about 78 A (calculated from 18 kW, 94% efficiency and 0.99 input PF). Plan protected DC cabling between UPS and battery cabinet, and a dedicated output distribution board, to local code.
Related Models
- S20K — same rating with 32 × 12 V / 7 Ah internal batteries.
- S15KL — 15 kVA long-backup.
- C10KL-Li / R10KL-Li — 10 kVA long-backup with lithium battery.
Frequently Asked Questions
Does the S20KL include the battery cabinet?
The UPS is listed with an external battery. Confirm the cabinet, battery type and quantity with Heizka in your quote request.
More models in the VRLA UPS range.
Ordering Information
| Voltrix Model | Form Factor | Apparent / Active Power | Battery | Part Number |
|---|---|---|---|---|
| S20KL | Tower | 20 kVA / 18 kW | Ext. Battery Cabinet | VTX-S20KL |
Downloads
Certifications & Warranty
Designed and manufactured under ISO 9001:2015. CE (EU Declaration of Conformity), IEC/EN 62040-1 (UPS Safety), IEC/EN 62040-2 (UPS EMC — Class C2), RoHS 2011/65/EU. 2-year UPS system warranty, return-to-base, parts and labour; 1-year VRLA battery warranty. 24/7 technical support with response within 4 hours.
Specifications subject to change without notice. Backup times are indicative and depend on load, temperature, battery age and discharge history. Voltrix is a registered brand of Heizka. All trademarks are property of their respective owners.